L7NH AL-71 — AL-71 Factory Setting
Trip — immediate stop
CAUSE
Why does it occur?
- Factory settings abnormality
- Reset the drive capacity and re-download the OS
REMEDY · Step by step
How to fix it?
- Check the drive capacity at device name [0x1008]; contact the service center
- If it recurs, replace the drive
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).
SOURCE
Related manual page
Verified · sol.ls-electric.com
Open PDF ↗L7NH Series AC Servo Drive User Manual V1.6 (EN)
p.375