breakerMetasol-MS/EOCRVerified · sol.ls-electric.com
Metasol-MS/EOCR STALL — Stall
Trip — immediate stop
CAUSE
Why does it occur?
- Stall
- Current stayed above the stall set level past the start time, indicating startup failure / run overload
REMEDY · Step by step
How to fix it?
Check the motor and driven load; clear the cause and verify the STALL setting.
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).
SOURCE
Related manual page
Verified · sol.ls-electric.com
Open PDF ↗LSIS EMPR (DMPi) Series Manual (E 09-1909)
p.18