InverterH100Verified · sol.ls-electric.com
H100 Over Voltage — Over Voltage
Trip — immediate stop
CAUSE
Why does it occur?
- DC circuit voltage exceeds specific value
- High input voltage, short Acc/Dec time, regenerative load
REMEDY · Step by step
How to fix it?
- Check input voltage
- Increase Acc/Dec time
- Use braking unit
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).
SOURCE
Related manual page
Verified · sol.ls-electric.com
Open PDF ↗H100 Troubleshooting Manual ENG Rev1.1 (240710)