H100 Thermal Trip — Thermal Trip
Trip — immediate stop
CAUSE
Why does it occur?
Motor overheat detected by external temperature sensor (PTC/PT100).
REMEDY · Step by step
How to fix it?
- Check motor temperature
- Check PTC/PT100 sensor
- Set PRT-34 for action mode
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).
SOURCE
Related manual page
Verified · sol.ls-electric.com
Open PDF ↗H100 Troubleshooting Manual ENG Rev1.1 (240710)
p.21