S100 OLt — Over Load
Trip — immediate stop
CAUSE
Why does it occur?
- Motor overload trip activated, actual load exceeds set level
- Operates when Pr.20 is set to non-zero
REMEDY · Step by step
How to fix it?
- Ensure motor and inverter have appropriate capacity
- Increase overload trip level (Pr.21)
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).