InverterS100Verified · sol.ls-electric.com
S100 ULt — Under Load
Trip — immediate stop
CAUSE
Why does it occur?
- Motor underload trip activated, actual load is less than set level
- Operates when Pr.27 is set to non-zero
REMEDY · Step by step
How to fix it?
- Check motor-load connection
- Reduce underload level set value (Pr.29, Pr.30)
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).
SOURCE
Related manual page
Verified · sol.ls-electric.com
Open PDF ↗S100 Simple Manual English V3.7 (240830)
p.186 · V3.7