iP5A Overlab — Overlab Error
Trip — immediate stop
CAUSE
Why does it occur?
- Two or more of the multi-function input terminals (M1–M
- are assigned to the same function — check the I/O group parameters IN-20 to IN-27
REMEDY · Step by step
How to fix it?
Check and correct duplicate multi-function input/output parameter settings (remove the double assignment of the same function)
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).