MR-J4 AL.51 — Overload 2
Trip — immediate stop
CAUSE
Why does it occur?
- - Maximum output current flowed continuously due to machine collision or the like. Detail No. Detail name Cause Check method Check result Action Target 51.1 Thermal overload error 3 during operation (
- The servo motor power cable was disconnected. Check the servo motor power cable. It is disconnected. Repair or replace the servo motor power cable. [A] [B] [WB] [RJ010] [GF] It is not disconnected.
REMEDY · Step by step
How to fix it?
Adjust the gain and acceleration/deceleration, and inspect the mechanism
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).