SINAMICS G120 F07015 — Motor temp sensor fault
Trip — immediate stop
CAUSE
Why does it occur?
PTC/KTY sensor open or short circuit
REMEDY · Step by step
How to fix it?
Check the sensor wiring and measure resistance; set P0601=0 if the sensor is not used
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).