SINAMICS G120 F30021 — Earth fault
Trip — immediate stop
CAUSE
Why does it occur?
Ground short on the output side or in the motor winding
REMEDY · Step by step
How to fix it?
Measure the motor insulation resistance and check the output cable insulation
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).