SINAMICS G120 F30011 — Line phase failure
Trip — immediate stop
CAUSE
Why does it occur?
One of L1/L2/L3 has lost phase, or excessive voltage imbalance
REMEDY · Step by step
How to fix it?
Check the input breaker/fuses, the NFB connection, and the transformer side
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).