SINAMICS G120 F07801 — Motor overcurrent
Trip — immediate stop
CAUSE
Why does it occur?
Output current exceeded the hardware limit — short circuit, ramp-up time too short, or motor parameter mismatch
REMEDY · Step by step
How to fix it?
Check the output for short circuit and ground fault, increase the ramp-up time P1120, and re-run auto-tuning (P1900)
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).