Below are a few steps to remedy for communication issues with MODBUS or RS485 communications. There is the protocol type selection, transmission speed and DATA Packet/CRC setup. Beyond that of physica
Often at times, it is desired to utilize frequency reference (analog input) loss detection where if the analog signal is lost or too high, the drive can fault ("Lost Command" or “LOr”) or keep running
The Lost Command is a common problem that comes up on startup. This is usually caused by the user accidently enabling a macro upon installation. The best way to fix this is to go to CNF43 and change t