iS7 Over Speed Trip — Over Speed Trip
Trip — immediate stop
CAUSE
Why does it occur?
- Motor speed exceeds overspeed detection level (PRT-
- for detection time (PRT-72). Vector control mode only.
REMEDY · Step by step
How to fix it?
- Check motor speed feedback
- Increase overspeed level
- Check encoder connection
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).