FR-A800 E.EF — External fault during output operation
Trip — immediate stop
CAUSE
Why does it occur?
- When the X32 signal turns OFF (the contact opens) due to an external fault or some other factor, the inverter output is shut off
- This function is available when "32" is set in any of Pr.178 to Pr.189 (Input terminal function selection)
- This protective function is not available in the initial statu
REMEDY · Step by step
How to fix it?
• Make sure that there is no problem in starting operation, and turn ON the X32 signal.
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).