FR-A800 E.USB — USB communication fault
Trip — immediate stop
CAUSE
Why does it occur?
The inverter output is shut off when the communication is cut off for the time set in Pr.548 USB communication check time interval. • Check that the USB communication cable is connected securely.
REMEDY · Step by step
How to fix it?
• Check the Pr.548 setting. • Connect the USB communication cable securely. • Increase the Pr.548 setting or set "9999." (Refer to page 719.)
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).