FR-A800 RB — Regenerative brake pre-alarm (Standard models only)
Alarm — operational, inspection needed
CAUSE
Why does it occur?
- Appears if the regenerative brake duty reaches or exceeds 85% of the Pr.70 Special regenerative brake duty value
- If the regenerative brake duty reaches 100%, a regenerative overvoltage (E
- OV[ ]) occurs. • Check if the brake resistor duty is not too high. • Check that the Pr.30 Regenerative functio
REMEDY · Step by step
How to fix it?
• Set the deceleration time longer. • Check the Pr.30 and Pr.70 settings. (Refer to page 743.)
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).