FR-A800 E.SER — Communication fault (inverter)
Trip — immediate stop
CAUSE
Why does it occur?
- The inverter output is shut off when communication error occurs consecutively for the permissible number of retries or more when Pr.335 RS-485 communication retry count ≠ "9999" during RS-485 communication through the RS-485 terminals
- The inverter output is also shut off if communication is broken
REMEDY · Step by step
How to fix it?
Perform wiring of the RS-485 terminals properly.
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).