FR-A800 E.PE6 — Fault
Trip — immediate stop
CAUSE
Why does it occur?
This protective function is activated by an inverter reset if writing data fails due to power-OFF or a data fault occurs in the storage device during parameter operations*1 or while the set frequency is written. • Check if the power was turned OFF during parameter operations. • Check if writing to E
REMEDY · Step by step
How to fix it?
- Check the power supply or the devices on the power system to check that the devices have no fault. • When E.PE6 occurs due to power-OFF during parameter operations: Check the read value of Pr.8
- When the value is "7" or smaller, perform All parameter clear and then an inverter reset. The parameter
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).
SOURCE
Related manual page
Summary based on the official Mitsubishi Electric manual. For accurate and complete information, always consult the official manual.