FR-A800 E.IPF — Instant Pwr failure
Trip — immediate stop· AUTO-RESET
CAUSE
Why does it occur?
- If a power failure occurs (or when power input to the inverter is shut off) for longer than 15 ms*6, the instantaneous power failure protective function is activated to shut off the inverter output in order to prevent the control circuit from malfunctioning
- If a power failure persists for 100 ms or
REMEDY · Step by step
How to fix it?
• Remedy the instantaneous power failure. • Prepare a backup power supply for instantaneous power failure. • Set the function of automatic restart after instantaneous power failure (Pr.57). (Refer to page 647 and page 654.)
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).