FR-A800 E.OC1 — Overcurrent trip during acceleration
Trip — immediate stop
CAUSE
Why does it occur?
When the inverter output current reaches or exceeds approximately 235%*1 of the rated current during acceleration, the protection circuit is activated and the inverter output is shut off. • Check for sudden speed acceleration. • Check if the downward acceleration time is too long in a lift applicati
REMEDY · Step by step
How to fix it?
- • Set the acceleration time longer. (Shorten the downward acceleration time of the lift.) • If "E.OC1" always appears at start, disconnect the motor once and restart the inverter
- If "E.OC1" still appears, contact your sales representative. • Check the wiring to make sure that output short circuit d
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).