FR-A800 E.OC2 — Overcurrent trip during constant speed
Trip — immediate stop
CAUSE
Why does it occur?
When the inverter output current reaches or exceeds approximately 235%*2 of the rated current during constant- speed operation, the protection circuit is activated and the inverter output is shut off. • Check for sudden load change. • Check for a short-circuit in the output circuit. • Check if the s
REMEDY · Step by step
How to fix it?
- • Keep the load stable. • Check the wiring to make sure that output short circuit does not occur. • Lower the stall prevention operation level
- Activate the fast-response current limit operation. (Refer to page 448.) • Check RS-485 terminal connection (under Vector control). • Prevent the motor from
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).