FR-A800 E.OLT — Stall prevention STP
Trip — immediate stop
CAUSE
Why does it occur?
- If the output frequency has fallen to 0.5 Hz by stall prevention operation and remains for 3 seconds, a fault (E.OLT) appears and the inverter is shut off
- OL appears while stall prevention is being activated
- When speed control is performed, a fault (E.OLT) appears and the inverter output is shut o
REMEDY · Step by step
How to fix it?
• Reduce the load. • Change the Pr.22, Pr.865, and Pr.874 values. (Check the Pr.22 setting under V/F control and Advanced magnetic flux vector control.) • For the test operation without connecting a motor, select the PM sensorless vector control test operation. (Refer to page 226.) • Also check that
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).