FR-A800 E.PE — Corrupt Memory
Trip — immediate stop
CAUSE
Why does it occur?
The inverter output is shut off if a fault occurs in the parameter stored. (EEPROM failure) Check for too many number of parameter write times.
REMEDY · Step by step
How to fix it?
- Contact your sales representative
- Set "1" in Pr.342 Communication EEPROM write selection (write to RAM) for the operation which requires frequent parameter writing via communication, etc
- Note that writing to RAM goes back to the initial status at power OFF
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).