FR-F800 CP — Parameter copy
Alarm — operational, inspection needed
CAUSE
Why does it occur?
- Appears when parameter copy is performed between inverters FR-F820-02330(55K) or lower, FR- F840-01160(55K) or lower, FR-F820-03160(75K) or higher and FR-F840-01800(75K) or higher
- Resetting of Pr
- 9, Pr
- 30, Pr
- 51, Pr
- 56, Pr
- 57, Pr
- 72, Pr
- 80, Pr
- 82, Pr
- 90 to Pr
- 94, Pr
- 453, Pr
- 455, Pr
- 458 to Pr
- 462, Pr
- 557, Pr
- 859, Pr
- 860 and Pr
- 893 is necessary
REMEDY · Step by step
How to fix it?
- Set the initial value in Pr
- 989 "Parameter copy alarm release"
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).