FR-F800 E.ILF — Input phase loss
Trip — immediate stop
CAUSE
Why does it occur?
- When Pr. 872 "Input phase loss protection selection" is enabled ("1") and one of the three-phase power input is lost, the inverter output is shut off. This protective function is not available when Pr. 872 is set to the initial value (Pr. 872 = "0"). (Refer to page 5-1
- Check for a break in the cable for the three-phase power supply input.
REMEDY · Step by step
How to fix it?
Wire the cables properly. Repair a break portion in the cable.
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).