FR-F800 E.OV3 — Regenerative overvoltage trip during deceleration or stop
Trip — immediate stop
CAUSE
Why does it occur?
- If regenerative power causes the inverter's internal main circuit DC voltage to reach or exceed the specified value, the protection circuit is activated to stop the inverter output
- The circuit may also be activated by a surge voltage produced in the power supply system. Check for sudden speed reduction. Check if the stall prevention operation is frequently activated in an application with a l
REMEDY · Step by step
How to fix it?
- Set the deceleration time longer. (Set the deceleration time which matches the moment of inertia of the load.) Make the brake cycle longer. Use the regeneration avoidance function (Pr
- 882 to Pr
- 886). (Refer to page 5-540.) Use the brake unit or power regeneration common converter (FR-CV) as required. Set Pr
- 154 "Voltage reduction selection during stall prevention operation" = "10, 11"
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).