InverterFR-F800Verification pending — cross-check with the official manual
FR-F800 E.PTC — E.PTC
Trip — immediate stop
CAUSE
Why does it occur?
- The inverter trips if resistance of the PTC thermistor connected between the terminal 2 and terminal 10 is equal to or higher than the Pr
- 561 "PTC thermistor protection level" setting for a continuous time equal to or longer than the setting value in Pr
- 1016 "PTC thermistor protection detection time"
- When the initial value (Pr
- 561 = "9999") is set, this protective function is not available.
REMEDY · Step by step
How to fix it?
Reduce the load.
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).