FR-F800 E.LCI — E.LCI
Trip — immediate stop
CAUSE
Why does it occur?
- The inverter trips when the analog input current is 2 mA or less for the time set in Pr
- 778 "4 mA input check filter"
- This function is available when Pr
- 573 "4 mA input check selection" = "2 or 3". (Refer to page 5-258.) This function is not available in the initial status. Check for a break in the wiring for the analog current input. Check that the Pr
- 778 setting is not too short
REMEDY · Step by step
How to fix it?
- Check the wiring for the analog current input. Set the Pr
- 778 setting larger
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).