FR-F800 E.P24 — E.P24
Trip — immediate stop
CAUSE
Why does it occur?
- When the 24 V DC power output from the PC terminal is shorted, this function shuts off the power output
- At this time, all external contact inputs switch OFF
- The inverter cannot be reset by entering the RES signal
- To reset it, use the operation panel, or switch power OFF, then ON again. Check for a short circuit in the PC terminal output. Check that the 24 V external power supply voltage is
REMEDY · Step by step
How to fix it?
- Repair the short-circuited portion. Supply the power at 24 V. (If the power at insufficient voltage is supplied to the 24 V input circuit for a long time, the inverter internal circuit may heat up
- Input power at correct voltage although it will not damage the inverter.)
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).