FR-F800 E.PCH — Pre-charge fault
Trip — immediate stop
CAUSE
Why does it occur?
- The inverter trips when the pre-charge time exceeds Pr
- 764 "Pre-charge time limit". The inverter trips when the measured value exceeds Pr
- 763 "Pre-charge upper detection level" during pre-charging. This function is available when Pr
- 764 and Pr
- 763 are set
- This protective function is not available in the initial status. Check that the Pr
- 764 setting is not too short. Check that the
REMEDY · Step by step
How to fix it?
- Set the Pr
- 764 setting longer. Set the Pr
- 763 setting larger. Set the Pr
- 127 setting higher. Check the connection to the pump
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).