FR-E800 E.AIE — Analog input fault
Trip — immediate stop
CAUSE
Why does it occur?
The inverter output is shut off when a 30 mA or higher current or a 7.5 V or higher voltage is input to terminal 2 while the current input is selected by Pr.73 Analog input selection, or to terminal 4 while the current input is selected by Pr.267 Terminal 4 input selection. (This protective function is available for the standard model, the Ethernet model, and the safety communication model.) Check
REMEDY · Step by step
How to fix it?
- Either give a current less than 30 mA, or set Pr.73, Pr.267, and the voltage/current input switch to the voltage input and input a voltage
- Reference manual FR-E800 Instruction Manual (Function)
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).