InverterFR-E800Verification pending — cross-check with the official manual
FR-E800 PS — PS
Alarm — operational, inspection needed
CAUSE
Why does it occur?
• The motor is stopped using the STOP/RESET key in the mode other than the PU operation mode. (To enable the STOP/RESET key in the mode other than the PU operation mode, set Pr.75 Reset selection/ disconnected PU detection/PU stop selection.) • The motor is stopped by the emergency stop function. • Check for a stop made by pressing the STOP/RESET key on the operation panel. • Check for whether the
REMEDY · Step by step
How to fix it?
- • Turn OFF the start signal and press the PU/EXT key for release. • Turn ON the X92 signal and OFF the start signal for release
- Reference manual FR-E800 Instruction Manual (Function)
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).