FR-E800 OLC — OLC
Alarm — operational, inspection needed
CAUSE
Why does it occur?
- • When the output current of the inverter increases, the stall prevention (overcurrent) function is activated. • The following section explains about the stall prevention (overcurrent) function
- During acceleration When the output current (output torque under Real sensorless vector control or Vector control) of the inverter exceeds the stall prevention level (Pr.22 Stall prevention operation level
REMEDY · Step by step
How to fix it?
- • Gradually increase or decrease the Pr.0 setting by 1% at a time and check the motor status. • Set a larger value in Pr.7 and Pr.
- • Reduce the load. • Try Advanced magnetic flux vector control, Real sensorless vector control, or Vector control. • Change the Pr.14 Load pattern selection setting. • The stall prevention operation current can be set in Pr.22 Stall prevention operation level. (The i
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).