FR-E800 E.OC2 — E.OC2
Trip — immediate stop
CAUSE
Why does it occur?
- When the inverter output current reaches or exceeds approximately 230%*2 of the rated current during constant- speed operation, the protection circuit is activated and the inverter output is shut off. • Check for sudden load change. • Check for output short-circuit. • Check if the stall prevention operation level is set too high
- Check if the fast-response current limit operation is disabled. • Ch
REMEDY · Step by step
How to fix it?
- • Keep the load stable. • Check the wiring to make sure that output short circuit does not occur. • Lower the stall prevention operation level
- Activate the fast-response current limit operation. • Prevent the motor from switching the rotation direction from forward to reverse (or from reverse to forward) during torque control under Real sensorless vector control. • Choose inverter and motor capac
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).