FR-E800 MT — MT
Alarm — operational, inspection needed
CAUSE
Why does it occur?
- Appears when the inverter's cumulative energization time reaches or exceeds the parameter set value
- Set the time until "MT" is displayed using Pr.504 Maintenance timer warning output set time (MT). "MT" does not appear when the setting of Pr.504 is the initial value ("9999")
- The set time of maintenance timer has been exceeded
REMEDY · Step by step
How to fix it?
- Take appropriate countermeasures according to the purpose of the maintenance timer setting
- Setting "0" in Pr.503 Maintenance timer clears the indication
- Reference manual FR-E800 Instruction Manual (Function)
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).