FR-E800 RB — RB
Alarm — operational, inspection needed
CAUSE
Why does it occur?
- Appears if the actual regenerative brake duty reaches or exceeds 85% of the reference regenerative brake duty (100%) determined by the settings of Pr.30 Regenerative function selection and Pr.70 Special regenerative brake duty
- If the regenerative brake duty reaches 100%, a regenerative overvoltage (E.OV[]) occurs. • Check if the brake resistor duty is not too high. • Check that the Pr.30 Regenera
REMEDY · Step by step
How to fix it?
- • Set the deceleration time longer. • Check the Pr.30 and Pr.70 settings
- Reference manual FR-E800 Instruction Manual (Function)
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).