InverterFR-E800Verification pending — cross-check with the official manual
FR-E800 EHR — EHR
Alarm — operational, inspection needed
CAUSE
Why does it occur?
Appears when Ethernet communication is interrupted by physical factors while Pr.1431 Ethernet signal loss detection function selection = "1 to 3". • Check for a break in the communication cable. • Check for a break in the Ethernet cable. • Check for any influence of noise.
REMEDY · Step by step
How to fix it?
- • Connect the Ethernet board securely. • Check that the Ethernet cable is connected to the Ethernet connector properly and the Ethernet cable is not damaged. • If there is noise interference, earth (ground) the shield of the Ethernet cable to the enclosure (as close as possible to the inverter) with a metal P-clip or U-clip to reduce noise on the Ethernet cable
- Reference manual FR-E800 Instructio
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).
SOURCE
Related manual page
Summary based on the official Mitsubishi Electric manual. For accurate and complete information, always consult the official manual.