FR-E800 IP — IP
Alarm — operational, inspection needed
CAUSE
Why does it occur?
Appears when the IP address or the subnet mask is out of the specified range. • Check that "0 or 255" is not set in the third or fourth octet of the IP address. • Check that the subnet mask setting is appropriate. • Check that the IP address settings are correct.
REMEDY · Step by step
How to fix it?
- • Set "1 to 254" in the third or fourth octet of the IP address. • Set the subnet mask (Pr.1438 to Pr.14
- correctly. • Set the IP address (Pr.1434 to Pr.14
- correctly. Reference manual FR-E800 Instruction Manual (Communication)
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).