FR-E800 E.CPU — Fault 5
Trip — immediate stop
CAUSE
Why does it occur?
The inverter output is shut off if the communication fault of the built-in CPU occurs. • Check for devices producing excess electrical noises around the inverter. • When Ethernet communication is used, check that the communication cable is connected properly. • Check if a cable is connected between terminals PC and SD. (E.6, E.7)
REMEDY · Step by step
How to fix it?
- • Take measures against noises if there are devices producing excess electrical noises around the inverter. • When Ethernet communication is used, connect the communication cable properly. • When a cable is connected between terminals PC and SD, remove the cable. (E.6, E.
- • Contact your sales representative. Reference manual • FR-E800 Instruction Manual (Function) • FR-E800 Instruction Manual (C
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).