V20 A501 — Current limit
Warning — monitor· AUTO-RESET
CAUSE
Why does it occur?
- Current limit warning
- Motor power does not correspond to inverter power, motor leads too long, or earth faults (see F1)
- Small motors (120 W) under FCC and light load may draw high current
REMEDY · Step by step
How to fix it?
- Follow F1 remedies
- For very small motors, use V/f operation
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).