V20 A911 — Vdc_max controller active
Warning — monitor· AUTO-RESET
CAUSE
Why does it occur?
- The Vdc_max controller is working to keep the DC-link voltage (r00
- below the level specified in r1242.
REMEDY · Step by step
How to fix it?
- Keep supply voltage within rating and match ramp-down time (P11
- to load inertia. Higher inertia needs longer ramp times; otherwise apply a braking resistor.
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).