V20 F60 — Asic timeout
Trip — immediate stop
CAUSE
Why does it occur?
- Internal communications failure. r0949=0 hardware-reported link fail; =1 software-reported link fail
- Can appear sporadically due to EMC problems
REMEDY · Step by step
How to fix it?
- Check the inverter
- If the fault appears sporadically, check and improve EMC and use an EMC filter
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).