L7N AL-15 — AL-15 Current Offset
Trip — immediate stop
CAUSE
Why does it occur?
- Abnormal current offset. The U/V/W phase current offset (0x2015-0x20
- is 5% or more of the rated current.
REMEDY · Step by step
How to fix it?
- Re-run the phase current offset adjustment
- If it still occurs, replace the drive
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).