L7N AL-24 — AL-24 Motor Cable Open
Trip — immediate stop
CAUSE
Why does it occur?
- Motor disconnection (motor cable open)
- Cause: motor cable disconnected, or U-V/V-W/W-U short inside the motor
REMEDY · Step by step
How to fix it?
- Check the motor cable for disconnection; check for U/V/W short inside the motor (replace motor)
- If it recurs after SVON, replace the drive
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).
SOURCE
Related manual page
Verified · sol.ls-electric.com
Open PDF ↗XDL-L7N 200V Series AC Servo Drive User Manual V1.7 (EN)
p.265