MR-JE AL.E0 — Excessive regenerative warning
Warning — monitor
CAUSE
Why does it occur?
- Regenerative load ratio exceeded 85% of the alarm level
- Regenerative energy is too high for the built-in resistor
REMEDY · Step by step
How to fix it?
- Review the duty cycle and deceleration time
- Add an external regenerative resistor if necessary
Do not reset repeatedly before identifying the cause. Repeated resets while ignoring a trip/alarm can cause secondary damage (IGBT failure, motor winding damage, etc.).
SOURCE
Related manual page
Summary based on the official Mitsubishi Electric manual. For accurate and complete information, always consult the official manual.